SERIES DETAILS
ADVANCE-GRP[GD] Series
Switched interlocked socket outlets [ATEX IECEx II 2 GD - GAS&DUST]

GENERAL DESCRIPTION PRODUCTS FOR USE IN A POTENTIALLY EXPLOSIVE ENVIRONMENT
Scame offers products suitable for installation into environments under potential risk of explosion identified as Zone 1/2 and 21/22 and that enter into the field of application for the ATEX Directive (European Directive 94/9/CE and IECEx).
REFERENCE STANDARDS
|
EN 60309-1
Plugs, socket outlets and couples for industrial purposes Part 1: General requirements. |
|
EN 60309-2
Plugs, socket outlets and couples for industrial purposes. Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonised configurations. |
|
EN 60309-4
Plugs, socket-outlets and couplers for industrial purposes. Part 4: Switched socket-outlets and connectors with or without interlock. |
|
EN 60079-0
Electrical apparatus for explosive gas atmospheres. Part 0: General requirements. |
|
EN 60079-31
Electrical apparatus for explosive gas atmospheres. Part 31: Equipment dust ignition protection by enclosure. |
|
EN 60079-1
Electrical apparatus for explosive gas atmospheres Part 1: Flameproof enclosures "d" |
|
EN 60079-7
Electrical apparatus for explosive gas atmospheres Part 7: Increased safety “e” |
|
IEC 60079-0
Electrical apparatus for explosive gas atmospheres. Part 0: General requirements. |
|
IEC 60079-31
Electrical apparatus for explosive gas atmospheres. Part 31: Equipment dust ignition protection by enclosure. |
|
IEC 60079-1
Electrical apparatus for explosive gas atmospheres Part 1: Flameproof enclosures "d" |
|
IEC 60079-7
Electrical apparatus for explosive gas atmospheres Part 7: Increased safety “e” |
|
TECHNICAL DATA SHEET
|
| Rated current |
16A-32A-63A-125A |
|
| Rated voltage |
50÷690V~ |
|
| Frequency |
50÷60Hz |
|
| Insulating voltage |
690V~ |
|
| Protection degree |
IP66 |
|
| Operating Temperature Range (16A-32A) |
-50°C to +60°C |
|
| Operating Temperature Range (63A-125A) |
-35°C to +60°C |
|
| Maximum permissible surface temperature |
T80°C (DUST) |
|
| Switched socket outlets with interlock material |
Thermosetting (GRP) |
|
| Impact resistance |
7J |
|
| Switch-disconnectors 16A-32A-63A |
COMMAND-EX Series |
|
| Switch-disconnectors 125A |
CZ0513 |
|
| Colour |
Black RAL9005 |
|
| ATEX Code |
II 2GD |
|
| Ex Protection type |
Ex d e IIC T4, T5, T6 Gb Ex tb IIIC T80°C Db IP66 |
|
| CE certificate - Certificate ATEX |
INERIS 15ATEX0017X |
|
| CE certificate - Certificate IECEx |
IECEx INE 15.0033X |
|
| Classe température et milieu (GAS) |
T4, T5, T6 |
|
BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS
|
| Saline solution |
Resistant
|
|
| Acids |
Concentrated |
Limited resistance
|
| Diluted |
Resistant
|
|
| Bases |
Concentrated |
Limited resistance
|
| Diluted |
Resistant
|
|
| Solvents |
Hexane |
Resistant
|
| Benzol |
Resistant
|
| Acetone |
Resistant
|
| Alcohol |
Resistant
|
|
| Mineral oil |
Resistant
|
|
| UV rays |
Resistant
|
|
|
|
|
|
|
|
| |
|
| |
|
|
|
|
| |
| |
|
|
|
|
|
Discover how to find in thousands configurations, the Combination unit for you. |
|
|
|
|